simple design

Stand-by  —  A  very  simple  design that  affects power  only  when  either  a lag/brownout  occurs  below,  or  a spike/surge occurs  above,  a  certain threshold.  When  either  occurs,  the  unit  trips  —  i.e.,  goes  into  battery mode.  This  "cleans"  the  voltage  and helps to  keep  any load  safe.  Industry  average "trip"  times  are  2–8 ms.  No  other  filtration  of  AC power  is  performed. •  Line  interactive  —  Constantly  monitors  inbound voltages,  and  uses  special  circuitry to  boost  low  voltages and clamp high  voltages  without  having to  use the batteries.  Indeed,  the  batteries  are  used  only  if  the input  voltage drops  below  acceptable levels  (typically  about  12%  below  normal),  goes  out  completely  or rises  to  dangerous  levels  (typically  about  14%  above  normal)  at  which  components  will be  damaged  if  line voltage  is  not removed.  Industry  average  transfer  time  is  1–3  ms. (If voltage  stays  within  its  normal window,  this  unit  continues to  pass  voltage,  unaltered,  from  the  wall.) •  On-line  (or  full on-line)  —  Constantly  filters the  power  and  performs  a function  known as  double conversion  (AC  to  DC  to  AC).  This  assures  that  the  load  —  in  this  case, phone  equipment  —  will receive not  only  uninterrupted,  true  sine  wave  output  but  also  the  cleanest,  steadiest  power  possible throughout any foreseeable  power  disruptions  or  voltage irregularities.  According to  industry  specs,  it  is  not  unusual for these  types  of  units  to  be  able  to  regulate  utility  power,  even  when  it  drops  to  27%  below  or  rises  to 33% above normal,  all  without  using  their  batteries. From  this  point,  UPSs  can be  further  broken  down  by  inverter  types,  which determine output.  These are: •  Square  wave. •  Modified sine  wave  (or  quasi  sine  wave). •  Sine wave.  Most  devices with  wall-mounted chargers,  such as cordless  drills  or  screwdrivers,  can  behave erratically  — sometimes  not  allowing the charge  circuit  to  engage  at  all  —  when  operating with  modified  sine  or  square wave inverters.  Small  wall-based transformer-style  power  supplies,  similar  to  those ESI  phone systems  use, can experience overheating  problems  with  modified  sine  or  square  wave  outputs,  which  occur  while  some UPSs  are operating in  battery mode.  This  overheating could  eventually  cause  damage to  the power  supplies; and,  in  time,  the  damage  could cause a  spike through the phone system  —  seriously  damaging some  of  the static-sensitive  components  inside the  casing.   While  the  true  sine wave UPS output  power  curve smoothly  increases  to  its peak,  then  smoothly   decreases  (allowing  connected  loads  and  equipment  to  operate  the  same  as  they  would  from  utility  supplied wall  power),  the  modified  sine  wave  and  square  wave  UPS  output  power curve  will shoot straight  up,  level  off at  peak  voltage and  then  drop  straight  down.  Additionally  troublesome is  that  the modified  sine  wave  sits  at zero  voltage for  a short  period  during the transition to  or  from  batteries  —  which is  the  main  difference between it  and the  square  wave  output  of  some  UPS.  Please  note  that  this  short  interval  during  which the modified  sine  wave  UPS sits  at  zero  voltage  can  directly  affect  the transfer  time  of  the UPS  and could, theoretically,  be  enough  to  cause  the  phone  equipment  to  reset  or  even  “freeze.” Though  it  is  hard  to  predict exactly  when  different  ESI  systems  will have  problems  with  modified  sine  wave  or square waveform  UPSs (meaning  during  a  power  failure  event  or  the recovery  from  one),  it’s  fair  to  assume that  a  problem  will eventually  arise  from  the  use  of  such  UPSs.  Therefore,  ESI  recommends that  only true sine  wave  output  UPSs  provide  backup  power to  our phone  systems  and  equipment.